dc.description.abstractExecutive Order (EO) 12902 requires that by 2005 the Federal Government including all U.S. Army installations reduce energy consumption by 30 percent as measured against energy consumption in the baseline year of 1985. To help the Army meet the goals of EO 12902, the U.S. Army Construction Engineering Research Laboratories (USACERL) conceived of the Model Energy Installation Program (MlEIP), a 5-year pilot project to investigate the feasibility of instituting energy efficiency on a basewide scale. As part of MEIP, USACERL surveyed the large boiler plants at Fort Hood, TX, to identify energy conservation opportunities (ECOs). The study found numerous opportunities to save energy. Most opportunities consisted of minor repiping, installation of new ancillary equipment. and installation of new, modulating-type burners. The total estimated cost to install all ECOs and address all safety issues is approximately $968,050. The estimated overall natural gas savings is 25 percent per year, or 85,350x 106 Btu per year. At a natural gas price of $3.93 per 1 x 106 Btu, the net savings are calculated to be $283,425, with an estimated simple payback period of 3.42 years.en_US
dc.description.sponsorshipStrategic Environmental Research and Development Program (U.S.)en_US
dc.format.extent88 pages / 19.09 MB-
dc.format.mediumPDF/A-
dc.language.isoen_USen_US
dc.publisherConstruction Engineering Research Laboratory (U.S.)en_US
dc.relation.ispartofseriesSpecial Report (Construction Engineering Research Laboratory (U.S.)) ; 96/57-
dc.rightsApproved for Public Release; Distribution is Unlimited-
dc.sourceThis Digital Resource was created from scans of the Print Resource-
dc.subjectUnited States.--Army--Facilities--Heating and ventilationen_US
dc.subjectEnergy consumption--Texasen_US
dc.subjectFort Hood (Tex.)en_US
dc.titleEvaluation of boiler plant energy conservation opportunities at Fort Hood, Texas : a study for the Army model energy installation programen_US
dc.typeReporten_US