Please use this identifier to cite or link to this item:
https://hdl.handle.net/11681/19915
Full metadata record
DC Field | Value | Language |
---|---|---|
dc.contributor | United States. Office of the Under Secretary of Defense for Acquisition, Technology, and Logistics | - |
dc.contributor.author | Beitelman, Alfred D. | - |
dc.contributor.author | McInerney, Michael K. | - |
dc.date.accessioned | 2016-10-12T14:03:37Z | - |
dc.date.available | 2016-10-12T14:03:37Z | - |
dc.date.issued | 2014-09 | - |
dc.identifier.uri | http://hdl.handle.net/11681/19915 | - |
dc.description | Technical Report | - |
dc.description | Abstract: This project demonstrated and validated a high-voltage capacitance-based water-treatment system for chilled-water cooling systems that was previously evaluated in separate work by the U.S. Army Engineer Research and Development Center, Construction Engineering Research Laboratory (ERDC-CERL). This emerging nonchemical technology, marketed as the Zeta Rod Water Management System, was shown to inhibit mineral scaling and biofouling in chilled-water systems without the need to use hazardous chemicals, including those typically applied to counteract the corrosive effects of conventional treatment chemicals. This project extended the earlier technology evaluation to four military installations with a variety of makeup water qualities and mechanical equipment. Demonstration results showed that this nonchemical water-treatment system effectively prevents corrosion, scaling, and biofouling in open-loop evaporative cooling towers using a wide range of makeup water chemistries (alkaline to acidic). It also can reduce system water usage by 20% because fewer blowdown cycles are needed to purge impurities, supporting DoD net zero water objectives for installations. A return-on-investment ratio of 3.37 was calculated. The validated applications are recommended for consideration by decision makers to reduce military installation chemical utilization and support Department of Defense Net Zero Water goals. | - |
dc.publisher | Construction Engineering Research Laboratory (U.S.) | - |
dc.publisher | Engineer Research and Development Center (U.S.) | - |
dc.relation | http://acwc.sdp.sirsi.net/client/en_US/search/asset/1036346 | - |
dc.rights | Approved for public release; distribution is unlimited. | - |
dc.source | This Digital Resource was created in Microsoft Word and Adobe Acrobat | - |
dc.subject | Capacitance-based water treatment | - |
dc.subject | Chilled-water cooling systems | - |
dc.subject | Corrosion Prevention and Control | - |
dc.subject | Demonstration | - |
dc.subject | Military installations | - |
dc.subject | Net Zero Water | - |
dc.subject | Corrosion Prevention and Control | - |
dc.title | Demonstration of noncorrosive, capacitance-based water-treatment technology for chilled-water cooling systems | - |
dc.type | Report | en_US |
Appears in Collections: | Technical Report |
Files in This Item:
File | Description | Size | Format | |
---|---|---|---|---|
ERDC-CERL-TR-14-15.pdf | 7.28 MB | Adobe PDF | View/Open |