Title: | Demonstration of a robust sensor system for remote condition monitoring of heat-distribution system manholes : final report on Project F09-AR03 |
Authors: | Mandaree Enterprise Corporation. GWA Research LLC. Department of Defense Corrosion Prevention and Control Program (U.S.) Palutke, Karl. Lux, Scott M. Marsh, Charles P. Clark, Larry. Phetteplace, Gary E. |
Keywords: | Corrosion prevention program (CPC) Heat distribution system Remote sensing Remote transmitting unit (RTU) Maintenance |
Publisher: | Construction Engineering Research Laboratory (U.S.) Engineer Research and Development Center (U.S.) |
Description: | Technical Report Abstract: This project demonstrated a wireless remote-monitoring system for detecting and reporting steam leaks or flooding in underground heat-distribution system (HDS) manholes. The system immediately notifies maintenance personnel of critical conditions that could indicate expensive energy losses and potentially serious damage to the HDS. Demonstrated at Redstone Arsenal, AL, the system used durable temperature and water-level sensors for operating in very high heat and humidity. Remote-monitoring nodes included remote transmitting units using one of two alternate wireless data technologies. Wireless 900 MHz Ethernet service was installed and commissioned for eight manholes, linking them to the Redstone supervisory control and data acquisition (SCADA) system, but full integration with the SCADA system was not feasible given limitations on installation resources. Cellular data service was installed for six other manholes and commissioned successfully. Those nodes functioned for about 15 months to record ambient manhole conditions and email daily rollup data to the project point of contact (POC), verifying continuous operation. The functionality of the system design was validated, but important lessons were learned about electric service availability, line-of-sight antenna positioning for wireless Ethernet, and RTU installation. The return on investment for the cellular system was 94.6, potentially saving $534,000 in maintenance over 30 years. |
Rights: | Approved for public release; distribution is unlimited. |
URI: | http://hdl.handle.net/11681/19740 |
Appears in Collections: | Technical Report |
Files in This Item:
File | Description | Size | Format | |
---|---|---|---|---|
ERDC-CERL-TR-16-2.pdf | 2.13 MB | Adobe PDF | ![]() View/Open |