Please use this identifier to cite or link to this item: https://hdl.handle.net/11681/11651
Full metadata record
DC FieldValueLanguage
dc.contributor.authorKorhonen, C. J. (Charles J.)-
dc.contributor.authorTobiasson, Wayne-
dc.date.accessioned2016-06-20T14:22:07Z-
dc.date.available2016-06-20T14:22:07Z-
dc.date.issued1980-03-
dc.identifier.urihttp://hdl.handle.net/11681/11651-
dc.descriptionSpecial Report-
dc.descriptionAbstract: We surveyed the roofs of seven buildings at Pease AFB with a hand-held infrared scanner to detect wet insulation. We used white spray paint to outline the wet areas and took core samples of the built-up membrane and insulation to verify our findings. Flashing defects around penetrations and bordering walls appear to be the major cause of the wet insulation found on these roofs. Since most problem areas are localized, we directed our repair recommendations toward salvaging as much of each roof as is economically possible.-
dc.publisherCold Regions Research and Engineering Laboratory (U.S.)-
dc.publisherEngineer Research and Development Center (U.S.)-
dc.relationhttp://acwc.sdp.sirsi.net/client/en_US/search/asset/1011841-
dc.relation.ispartofseriesSpecial report (Cold Regions Research and Engineering Laboratory (U.S.)) ; 80-14.-
dc.rightsApproved for public release; distribution is unlimited.-
dc.sourceThis Digital Resource was created from scans of the Print Resource-
dc.subjectBuilt-up roofs-
dc.subjectRoofing-
dc.subjectThermograms-
dc.subjectInfrared scanning-
dc.subjectInsulation-
dc.subjectMoisture-
dc.subjectRoofs-
dc.subjectPease Air Force Base, New Hampshire-
dc.subjectCRREL ROOF MOISTURE SURVEY, PEASE AFB-
dc.subjectBUILDINGS 35, 63, 93,112,113,120 and 220-
dc.titleCRREL roof moisture survey, Pease AFB buildings 35, 63, 93, 112, 113, 120 and 220-
dc.typeReporten_US
Appears in Collections:Special Report

Files in This Item:
File Description SizeFormat 
SR-80-14.pdf7.55 MBAdobe PDFThumbnail
View/Open